Air Flow Anemometer
Keywords: air flow anemometer, AMF028+ anemometer, digital anemometer, duct air flow meter, vane anemometer
Digital air flow anemometer with a 0–45 m/s vane probe, CMM/CFM duct flow, 500-record memory and USB connection to a PC.
The AMF028+ is a vane anemometer for measuring both wind velocity and duct air flow. Velocity is read from the rotating vane in m/s, ft/min, knots, km/h or mph, while air flow is calculated in CMM or CFM — enter the duct area and the instrument works out the volume directly instead of leaving the conversion to the user.
The same probe also measures air temperature, so a single visit records both the flow and the conditions behind it. Results can be held, stored or deleted on the spot, up to 500 records are kept in memory, and the USB cable lets the stored data be transferred to a PC. A retractable drag rod extends the probe into ductwork that would otherwise be out of reach.

AMF028+ Digital Air Flow Anemometer | 500 Records
1. Vane Anemometer and Flow Meter — measures wind velocity and calculates air flow volume in CMM or CFM.
2. 0–45 m/s Velocity Range — covers low duct velocities up to strong airflow, with 0.001 m/s resolution.
3. Duct Area Calculation — entering the duct area lets the instrument compute flow directly, with 2/3 Vmax and average flow modes.
4. Air Temperature Measurement — 0–45 °C with 0.1 °C resolution and ± 1.0 °C accuracy.
5. 500-Record Memory — results can be held, stored and deleted, with up to 500 records kept on board.
6. USB Connection to PC — stored data can be transferred to a computer for reporting.
7. Retractable Drag Rod — extends the probe so measurements can be taken inside ductwork.
8. Five Velocity Units — m/s, ft/min, knots, km/h and mph, switchable on the spot.
9. Large LCD Display — clear four-digit main display with a secondary temperature line.
10. Audio Key Alert and Backlight — audible key feedback and a backlight for dim plant rooms.
11. Auto Power Off — switches off after 10 minutes without operation to save battery.
12. Low Battery Indication — warns before the AAA cells are too weak for accurate readings.
Close-up of the display and control panel.
|
Close-up of the vane probe head and sensor.
|
Keypad, retractable drag rod and USB cable detail.
|
| Model | AMF028+ |
| Product Name | Digital Air Flow Anemometer |
| Wind Velocity Range | 0.00–45.0 m/s (0–8800 ft/min; 0–88.0 knots; 0–140.0 km/h; 0–100 mph) |
| Velocity Resolution | 0.001 m/s (0.01 ft/min, knots, km/h; 0.001/0.01 mph) |
| Velocity Accuracy | ± 3 % ± 0.1 m/s |
| Air Flow Range | 0–999900 m³/min (CMM); 0–999900 ft³/min (CFM) |
| Air Flow Resolution | 0.001–100 depending on range |
| Duct Area Setting | 0.001–9999 |
| Air Temperature Range | 0–45.0 °C / 32.0–113.0 °F |
| Temperature Resolution / Accuracy | 0.1 / ± 1.0 °C; ± 1.8 °F |
| Functions | Data holding, storing and deleting; unit conversion; max / min velocity; 2/3 Vmax and average flow |
| Memory | 500 records |
| Interface | USB connection to PC with bundled software |
| Power | 4 × 1.5 V AAA battery |
| Auto Power Off | 10 minutes without operation |
| Accessories | Auxiliary fan, software disc, USB cable, 4 × AAA battery, PP packing box |
1. HVAC commissioning and balancing of supply and exhaust ductwork.
2. Industrial ventilation checks in plant rooms, workshops and clean rooms.
3. Air flow surveys for fume hoods, drying tunnels and process equipment.
4. Field measurement where velocity, duct flow and temperature must be recorded together.